OutBack Power EnergyCell® High-Capacity 48V 810Ah VRLA Sealed Deep-Cycle Battery Bank w/ Integrated Rack System (800RE)
$14,103.00
Product Images: Images are provided for illustrative purposes only and may not reflect the exact appearance, components, packaging, labeling, or configuration of the product received. Please refer to the product description and specifications for complete product details.
Frequently bought together:
Description
| Model | 800RE |
| Nominall Voltage Per Cell | 2V |
| Capacity 20Hr Rate (1.75VPC) | 672 |
| Capacity 100Hr Rate (1.75VPC) | 810 |
| Watts Per Cell 15min Rate (1.67VPC) | 1230 |
| Cycle Life 50% DOD (77°F/25°C) | 1800 cycles |
| Optimal Operating Temperature Range | 73.4 to 78.8°F (23 to 26°C) |
| OCV Per Cell Limit * | 2.05 |
| Initial Charge Voltage Per Cell ** | 2.27 |
| Float Voltage Per Cell (77°F/25°C) | 2.25 |
| Float Voltage Per Cell (95°F/35°C) | 2.21 |
| Equalize Voltage Per Cell (69.8 to 89.6°F/21 to 32°C) | 2.32 |
| Maximum Charge Current (A) | 148.75 |
| Shelf Life (77°F/25°C) | 6 months |
| Short Circuit Current (A) | 4728 |
| Internal Resistance (micro Ω) | 441 |
| Terminal Torque (Intercell Connects) | 88 in-lbs |
| Hardware Specification (Intercell Connects) | M8 bolt, lock and flat washer |
| Weight Per Cell (lbs/kg) | 114.3 / 51.8 |
| Dimensions Per Cell L x W x H (in/mm) | 21.8 x 6.5 x 11.9 / 554 x 165 x 302 |
* Before installation, OCV is open circuit voltage. ** Represents 60Hrs charge time at 16 to 32°C.
• Equalize in the following conditions if float voltage of any cell is less than 2.17VPC or the float voltage range after 6 months is outside the ±0.08V of Nominall setting
• 24Hrs after current stabilization, (3Hrs without charge), at ambient temperatures from 70 TO 90°F (21 TO 32°C)